Resource search

Search DataDrivenAEC

Open the full search page →

Transmission + infiltrationBTU/h · kWFree

Heating Load
Calculator

Combine verified envelope-transmission and entered infiltration inputs for a steady-state heat-loss sensitivity. This is not a complete load calculation or equipment selection.

Who it's for: mechanical engineers and building designers sizing heating systems for residential or light-commercial projects — you'll need the exposed envelope area, an area-weighted average U-value, and the ASHRAE 99% winter design temperature for the project location, typically at schematic design.

Q = U·A·ΔT + CFM·entered air factor·ΔT
Every project value—including ACH and the sensible-air factor—is entered by the user. The worksheet does not select weather, infiltration, ventilation, assemblies, diversity, equipment, or safety factors.
Heating Load
BTU/h · kW

How to use this calculator

1
Enter the floor area and ceiling height
Total conditioned floor area in ft² and the typical floor-to-ceiling height — multiplied together to give the building interior volume used in the infiltration calculation.
2
Enter the exposed envelope area
Combined area of all heat-losing surfaces facing outdoor or unconditioned conditions: exterior walls, roof, windows, and doors. Sum these in ft².
3
Enter the average envelope U-value
Area-weighted thermal transmittance in BTU/h·ft²·°F. Compute U = 1 ÷ R-total for each surface type, multiply by its area share, then sum across the whole envelope.
4
Set the indoor and outdoor design temperatures
Use 70°F for the indoor setpoint; find the 99% winter design dry-bulb temperature for your project city in ASHRAE Handbook of Fundamentals (Table 1 climatic data).
5
Set the infiltration rate (ACH)
Air changes per hour at natural conditions. Use 0.25–0.5 ACH for tight modern construction, 0.75–1.0 for average, and up to 1.5 ACH for older leaky buildings.
6
Read the design heating load
Total BTU/h and kW — the minimum output the heating system must supply on the design day. The badge shows load intensity (BTU/h·ft²) as a sanity check; 10–25 is typical for well-insulated buildings.

The formula

A building loses heat through its envelope (conduction across walls, roof, and windows) and through cold air infiltrating from outside. The total rate on the coldest design day sets the minimum boiler or furnace output.

Qtotal = U · A · ΔT + 1.08 · CFM · ΔT
where CFM = ACH × Volume ÷ 60

U = average envelope U-value (BTU/h·ft²·°F) — the reciprocal of total R-value
A = exposed envelope area (ft²) — walls, roof, windows, and doors combined
ΔT = indoor setpoint − outdoor 99% design temperature (°F)
CFM = infiltration airflow in cubic feet per minute
1.08 = sensible heat factor for air at standard conditions (BTU/h per CFM per °F)
kW = Qtotal ÷ 3,412

Worked example

Example
A 1,800 ft² single-story house with 9 ft ceilings has an exposed envelope of 2,600 ft² at an area-weighted average U = 0.08 BTU/h·ft²·°F. The indoor setpoint is 70°F; the local 99% design outdoor temperature is 10°F; infiltration is 0.5 ACH. ΔT = 70 − 10 = 60°F. Transmission = 0.08 × 2,600 × 60 = 12,480 BTU/h. Volume = 16,200 ft³; CFM = 0.5 × 16,200 ÷ 60 = 135 CFM; infiltration = 135 × 1.08 × 60 = 8,748 BTU/h. Design load = 21,228 BTU/h (6.2 kW).

When this estimate will be off

  • Solar and internal gains are intentionally excluded — this gives a conservative peak-loss result, which is standard for heating equipment sizing. Including gains would reduce the calculated load.
  • Assumes one uniform U-value for the entire envelope. Real buildings have walls, windows, and roofs at very different U-values; compute the area-weighted average before entering or the result will be inaccurate.
  • The ACH infiltration estimate is a rough whole-building figure. ACCA Manual J uses infiltration class tables tied to construction quality and local wind exposure — blower-door test results give a more accurate ACH.
  • Covers only the two displayed steady-state terms. Ventilation, zoning, thermal bridges, ground coupling, transient effects, controls, distribution losses, equipment performance and selection are outside the worksheet.

Frequently asked questions

A common mistake: Solar and internal gains are intentionally excluded — this gives a conservative peak-loss result, which is standard for heating equipment sizing. Including gains would reduce the calculated load.

It is the sensible heat capacity of air at standard conditions: air density (~0.075 lb/ft³) × specific heat (0.24 BTU/lb·°F) × 60 min/h ≈ 1.08 BTU/h per CFM per °F. Multiplying by CFM and ΔT converts the infiltration airflow into a heat-loss rate.

ASHRAE recommends the 99% heating design dry-bulb temperature — the value exceeded 99% of hours in the heating season for that city. It is listed in ASHRAE Fundamentals Table 1 (climatic design conditions) for hundreds of locations. Using a warmer value under-sizes equipment; a colder value adds safety margin.

For each surface type (wall assembly, roof, window, door) calculate U = 1 ÷ R-total. Multiply each U by its area, sum across all surfaces, then divide by the total exposed area. For reference: code-minimum walls are roughly U-0.064–0.080; double-pane windows around U-0.30–0.40. A composite below U-0.10 indicates a well-insulated envelope.

It gives the design load the system must meet — a reliable starting point. Equipment is typically selected at 1.15–1.25× the calculated load to account for duct or piping losses and allow warm-up recovery. ACCA Manual J is the standard method for final residential equipment sizing; this calculator is a preliminary screen.

Sources

  • ASHRAE Handbook of Fundamentals Ch. 18 — design heating load calculation method: U·A·ΔT for transmission, 1.08·CFM·ΔT for sensible infiltration
  • ACCA Manual J (8th ed.) — residential load calculation standard; defines design conditions, infiltration classes, and construction factors

This free Heating Load Calculator is built and maintained by DataDrivenAEC, using the relevant codes and standards. It does not substitute for professional judgment.