R-Value ↔ U-Value
Converter
Convert between thermal resistance (R) and transmittance (U), and between metric and imperial units. Enter any one value and get the other three: R and U in both SI and US units.
Who it's for: architects and energy designers moving thermal numbers between material datasheets and code checks. Enter any one R or U value; the tool returns all four. It uses U = 1/R within a unit system and R(imperial) = R(SI) × 5.678 between systems, at construction documents.
How to use this calculator
The formula
Worked example
When this estimate will be off
- Surface-to-surface values only — does not include the still-air films on each face. For a whole-assembly U-value per ISO 6946, add interior surface resistance (Rsi 0.13 m²K/W) and exterior surface resistance (Rse 0.04 m²K/W) to the layer sum before inverting.
- No thermal bridging — studs and framing carry heat at much higher U-values than the insulated cavity. Use a parallel-path or isothermal-planes method for framed wall assemblies.
- Single-value conversion only — if you have multiple material layers, sum all layer R-values first, then convert or invert the total.
- R-values are measured under standard lab conditions; field performance shifts slightly when insulation is compressed, wet, or exposed to extreme temperatures.
Frequently asked questions
A common mistake: Surface-to-surface values only — does not include the still-air films on each face. For a whole-assembly U-value per ISO 6946, add interior surface resistance (Rsi 0.13 m²K/W) and exterior surface resistance (Rse 0.04 m²K/W) to the layer sum before inverting.
U-value is the reciprocal of R-value within one unit system: U = 1 ÷ R. R-value measures thermal resistance, while U-value measures heat transmittance. A layer with R = 2.29 m²K/W has U = 0.437 W/m²K. Raise the R-value and the U-value falls; the two always move in opposite directions.
Divide the imperial R-value by 5.678263. Imperial R is measured in ft²·°F·h/BTU and SI R in m²K/W, and that factor carries the unit change. An R-13 batt becomes 13 ÷ 5.678263 = 2.29 m²K/W. To go the other way, multiply the SI R-value by 5.678263.
A lower U-value means less heat passes through the tested layer or assembly for each degree of temperature difference, while a higher R-value means more resistance to that flow. This converter does not select a code, certification, or project target.
These figures are surface-to-surface. A whole-assembly U-value also adds the still-air films on each face. ISO 6946 gives an interior Rsi of 0.13 m²K/W and an exterior Rse of 0.04 m²K/W for horizontal heat flow. Add both to the layer R-values before inverting, so total R = Rsi + ΣR + Rse.
Sources
- ISO 6946:2017 — Building components and elements — thermal resistance and transmittance — calculation methods, including the standard surface resistances Rsi and Rse.
- IECC 2021 Table R402.1.2 — US minimum insulation R-values by climate zone for ceilings, walls, floors, and windows — the code context where these conversions appear most often.
This free R-Value ↔ U-Value Converter is built and maintained by DataDrivenAEC, using the relevant codes and standards. It does not substitute for professional judgment.