Cleanroom HVAC
Sizing
Required supply airflow for a cleanroom from its volume and the air-change rate for the target ISO cleanliness class. Pick a class for a typical ACH, then refine to your design value.
Who it's for: mechanical engineers and cleanroom designers verifying that a proposed HVAC system delivers the air-change rate required by the ISO 14644 cleanliness class — you need the room's floor area, ceiling height, and a target ACH.
How to use this calculator
The formula
Metric: Q (m³/h) = ACH × V
Imperial: Q (CFM) = ACH × V ÷ 60
Q = required supply airflow (m³/h or CFM)
ACH = air changes per hour for the ISO class (ISO 7 typical: 30–60)
V = room volume = floor area × ceiling height (m³ or ft³)
Worked example
When this estimate will be off
- Non-unidirectional rooms only — ISO 5 and cleaner are designed on face velocity (~0.45 m/s), not ACH; this calculator gives an indicative number, not a compliant design for those classes.
- ACH midpoints are typical design ranges from ISO 14644-4 guidance. Your final ACH must be validated against the actual contamination control strategy and qualification (DQ/OQ/PQ) requirements.
- Does not include make-up air for positive-pressure offset or local exhaust compensation — add 10–15% over the ventilation demand for a pressurised cleanroom suite.
- Assumes a uniform ceiling height. Rooms with raised-floor plenums, equipment coffers, or split levels need the volume calculated by zone.
Frequently asked questions
ISO 14644 defines cleanliness by particle count, not a mandatory ACH. Typical design ranges used in practice are ISO 5 ≈ 240–600, ISO 6 ≈ 90–180, ISO 7 ≈ 30–60, and ISO 8 ≈ 10–25 ACH. The calculator pre-fills the midpoint; validate your design ACH against the contamination control strategy and qualification data.
At ISO 5 and cleaner, airflow is unidirectional — a laminar-flow ceiling or wall panel sweeps particles away rather than diluting them. The design parameter is face velocity (~0.45 m/s) over the supply area, not total ACH. ACH-based sizing underestimates supply for these classes. Confirm with ISO 14644-3 performance testing after installation.
Yes. A positive-pressure cleanroom typically needs 10–15% additional supply above the ventilation demand to overcome leakage through doors, pass-throughs, and wall cracks. Add this offset to the calculator result. The HVAC designer must also verify that exhaust, recirculation, and make-up air balance correctly across the whole suite.
Total supply airflow — all conditioned air delivered to the room, most of which is recirculated through HEPA filters. Fresh (outside) air is a small fraction, sized for occupant ventilation and pressure offset. Confirm the fresh-air split with the project mechanical engineer and the room's occupancy load.
Sources
- ISO 14644-1:2015 — classification of air cleanliness by particle concentration — defines ISO classes 1–9 and the particle-count limits for each
- ISO 14644-4:2001 — cleanroom design and construction — HVAC sizing guidance and typical air-change rates by ISO class
This free Calculator is built and maintained by DataDrivenAEC, using the relevant codes and standards. It does not substitute for professional judgment.