FeaturedOpportunity Radar20,000+ opportunities tracked worldwide, filtered for your expertise.One-time report — $29 $9.90 →
ISO 14644Air changes/hrFree

Cleanroom HVAC
Sizing

Required supply airflow for a cleanroom from its volume and the air-change rate for the target ISO cleanliness class. Pick a class for a typical ACH, then refine to your design value.

Who it's for: mechanical engineers and cleanroom designers verifying that a proposed HVAC system delivers the air-change rate required by the ISO 14644 cleanliness class — you need the room's floor area, ceiling height, and a target ACH.

Airflow = ACH × volume / 60
Typical recommended air-change rates (ISO 14644): ISO 5 ≈ 240–600, ISO 6 ≈ 90–180, ISO 7 ≈ 30–60, ISO 8 ≈ 10–25 ACH. Unidirectional (ISO 5 and cleaner) is usually designed on face velocity (~0.45 m/s), not ACH — treat this as a non-unidirectional estimate.
Supply Airflow
CFM · m³/h

How to use this calculator

1
Choose units
Select Metric (m, m³/h) or Imperial (ft, CFM) to match your project drawings and specifications.
2
Enter the floor area
The internal floor area of the cleanroom in the selected unit — do not include wall thickness or adjacent corridors.
3
Enter the ceiling height
The clear height from finished floor to ceiling; multiplied by floor area to give room volume.
4
Pick the ISO class
Sets the mid-range ACH for that class as a starting point — ISO 7 pre-fills 45 ACH, reflecting the typical 30–60 ACH design range.
5
Adjust air changes per hour
Override the class default with your design ACH if your contamination control strategy calls for a value outside the typical range.
6
Read the required supply airflow
The result shows total supply airflow in both m³/h and CFM, with room volume as a reference check.

The formula

In plain terms: the supply airflow is the room volume multiplied by how many complete air changes per hour the cleanliness class requires. In metric the result is already in m³/h; in imperial divide by 60 to convert the hourly volume to cubic feet per minute.

Metric: Q (m³/h) = ACH × V
Imperial: Q (CFM) = ACH × V ÷ 60

Q = required supply airflow (m³/h or CFM)
ACH = air changes per hour for the ISO class (ISO 7 typical: 30–60)
V = room volume = floor area × ceiling height (m³ or ft³)

Worked example

Example
A pharmaceutical lab designed to ISO 7 has a floor area of 50 m² and a ceiling height of 3 m, giving a room volume of 150 m³. At the mid-range ACH for ISO 7 (45 ACH), the required supply airflow is 45 × 150 = 6,750 m³/h (≈ 3,973 CFM). This is the ventilation demand before adding 10–15% for positive-pressure make-up air.

When this estimate will be off

  • Non-unidirectional rooms only — ISO 5 and cleaner are designed on face velocity (~0.45 m/s), not ACH; this calculator gives an indicative number, not a compliant design for those classes.
  • ACH midpoints are typical design ranges from ISO 14644-4 guidance. Your final ACH must be validated against the actual contamination control strategy and qualification (DQ/OQ/PQ) requirements.
  • Does not include make-up air for positive-pressure offset or local exhaust compensation — add 10–15% over the ventilation demand for a pressurised cleanroom suite.
  • Assumes a uniform ceiling height. Rooms with raised-floor plenums, equipment coffers, or split levels need the volume calculated by zone.

Frequently asked questions

ISO 14644 defines cleanliness by particle count, not a mandatory ACH. Typical design ranges used in practice are ISO 5 ≈ 240–600, ISO 6 ≈ 90–180, ISO 7 ≈ 30–60, and ISO 8 ≈ 10–25 ACH. The calculator pre-fills the midpoint; validate your design ACH against the contamination control strategy and qualification data.

At ISO 5 and cleaner, airflow is unidirectional — a laminar-flow ceiling or wall panel sweeps particles away rather than diluting them. The design parameter is face velocity (~0.45 m/s) over the supply area, not total ACH. ACH-based sizing underestimates supply for these classes. Confirm with ISO 14644-3 performance testing after installation.

Yes. A positive-pressure cleanroom typically needs 10–15% additional supply above the ventilation demand to overcome leakage through doors, pass-throughs, and wall cracks. Add this offset to the calculator result. The HVAC designer must also verify that exhaust, recirculation, and make-up air balance correctly across the whole suite.

Total supply airflow — all conditioned air delivered to the room, most of which is recirculated through HEPA filters. Fresh (outside) air is a small fraction, sized for occupant ventilation and pressure offset. Confirm the fresh-air split with the project mechanical engineer and the room's occupancy load.

Sources

  • ISO 14644-1:2015 — classification of air cleanliness by particle concentration — defines ISO classes 1–9 and the particle-count limits for each
  • ISO 14644-4:2001 — cleanroom design and construction — HVAC sizing guidance and typical air-change rates by ISO class

This free Calculator is built and maintained by DataDrivenAEC, using the relevant codes and standards. It does not substitute for professional judgment.